Outdoor airflow into HVAC systems: An evaluation of measurement technologies
Publication Type
Report
  
  
      Authors
Abstract
During the last few years, new technologies have been introduced for measuring the flow rates of outdoor  air (OA) into HVAC systems; however, an evaluation of these measurement technologies has not  previously been published. This document describes a test system and protocols developed for controlled  evaluation of these measurement technologies. The results of tests of three measurement technologies are  also summarized. The test system and protocol were judged practical and very useful. The test results  indicate that one measurement technology can measure OA flow rates with errors of 20% or less without a  field-based calibration, as long as the OA velocities are sufficient to provide an accurately measurable  pressure signal. The test results for a second measurement technology are similar; however, a difficult  field-based calibration relating the OA flow rate with the pressure signal would be required to reduce errors  below approximately 30%. The errors in OA flow rates measured with the third measurement technology,  that uses six electronic airspeed sensors downstream of the OA inlet louver, exceeded 100%; however,  these errors could be substantially reduced through a difficult field based calibration. The effects of wind  on the accuracy of these measurement technologies still needs to be evaluated.
  
  
  
      Year of Publication
2003
  
  
  
  
  
      Organization
      Indoor Environment Group, Systems and Energy Technologies Analysis Department, Energy Analysis Division